MinStroy Russia published instructions for safe use of gas in everyday life. Project on approval of the instruction on the safe use of gas while satisfying the utility domestic needs instruction on the safe use of gas in everyday life

MinStroy Russia published on the safe use of natural gas in domestic conditions. The document was approved by the Order of the Ministry, after registering in the Ministry of Justice of the Russian Federation, the instruction will become mandatory for use in all regions. This was reported today by the head of the Ministry of Construction of Russia Mikhail Men in the framework of the Council of the President of the Russian Federation with members of the country's government.

"The instruction contains rules for the behavior of management companies, homeowners' partnerships, individual entrepreneurs, owners and tenants of premises in apartment buildings, aimed at the safe use of gas in the satisfaction of communal domestic needs," Minister reported at the meeting.

For example, management organizations are required to check the state of the flue and ventilation channels, control the quality and timely execution of their maintenance of maintenance in good condition, at least once every 10 days to check the basements for gas supply with the recording of results in special journals.

Individual entrepreneurs, owners and tenants of premises are required to allow at any time of day to premises in which gas equipment, emergency service workers for the prevention, localization and elimination of accidents arising from its operation. And also contain flue and ventilation channels in proper technical condition and at no circumstances do not interfere in their work on their own.

The document also provides for an instruction on the safe use of gas and an exemplary list of topics for the primary briefing of gas consumers.

"The bill, tightening control over the maintenance of domestic gas equipment developed by the Ministry of Travel of Russia, adopted by the State Duma in the first reading, and the Government of Russia has already been amended, according to which the government will not only endowed with the authority to establish requirements for companies serving in-house gas equipment, but also apply Administrative punishment to owners who violate elementary safety rules when handling gas equipment and ignore the prescriptions of specialized companies. As a proactive measure, we have developed an instruction that will help even adopt the law to reduce the risks of incorrect installation and operation of gas equipment, "Mikhail Mikhail Maxim commented on the head of the Ministry of Transport

Instructions for safe use of gas when satisfying communal domestic needs.

The instructions are required for officials of the departments and organizations responsible for the safe operation of the gas farms of residential buildings regardless of departmental affiliation, and for the population using gas in the satisfaction of public utilities, in the territory of the Russian Federation. Responsibility for the safety of gas equipment and the good condition of the flue and ventilation channels, as well as the sealing of engineering communications entries in residential buildings is imposed on the heads of housing and operational organizations, in housing cooperatives - on their chairmen, in homes and apartments belonging to citizens on personal property rights, - owners (users).

Responsibility for the safe operation of working household gas devices in homes and apartments, the maintenance of their maintenance in accordance with the requirements of the instructions (users).

1. Housing and operational organizations(partnerships of housing owners, housing cooperatives or other specialized consumer cooperatives; management organizations, or with direct management - the owners of the premises in an apartment building) should:

1.1 provide specialized organizations with comprehensive assistance in carrying out the maintenance of gas equipment and propaganda of the safety of the gas population.

electric lighting and ventilation. Monitor places in the intersections of internal gas pipelines and building elements of buildings, sealing of inputs in the building of engineering communications.

1.3 Provide at any time of day the unhindered access of workers of specialized organizations in cellars, technical underground to test them for gaspace.

1.4 Provide a timely check of the state of chimneys, ventilation channels and chimney headings, carry out control over the quality of their inspection, to provide on time to enterprises of gas farms in the health of chimneys and ventilation channels.

1.5 Immediately report specialized organizations on the need to turn off gas devices when identifying the chimney and unauthorized installation.

1.6 Settlement of gasified apartments (primary check-in, when exchanging) only after the owners of the tenants with a specialized organization in the presence of a confirmation document.

1.7 Call a representative of a specialized organization to turn off gas devices when leaving tenants from the apartment.

2. Owners (users) Apartments (households) Using gas to everyday life, are required:

2.1 Turn into instruction on the safe use of gas in the operational specialized organization, to have and comply with the instructions instructions.

2.2 Monitor the normal operation of gas devices, chimneys and ventilation, check the traction to the inclusion and during the operation of gas devices with the tap of gas combustion products into the chimney. Before using the gasified furnace, check whether the Schieber is open. Periodically purify the "pocket" chimney.

2.3 At the end of the use of gas, close the cranes on gas devices and in front of them, and when placing cylinders inside the kitchens, additionally close the valves from cylinders.

2.4 In case of gas equipment malfunction to cause employees of a specialized organization.

2.5 In case of a sudden cessation of gas supply to close the gas appliances burners immediately and inform the specialized organization by telephone 04.

2.6 If the gas smell appears in the room, immediately stop using gas devices, block the taps to the instruments and on the instruments, open windows or windows to carry out the room, cause the emergency service of a specialized organization by calling 04 (outside the ridden room). Do not light fire, do not smoke, do not include and not turn off the electric light and electrical appliances, do not use the electrical connections.

2.7 Before entering the basements and cellar, to the inclusion of light or ignition fire, make sure that there is no smell of gas.

2.8 When the smell is discovered in the basement, the entrance, in the courtyard, on the street:

Tell those surrounding about precautions;

Report in the emergency dispatch service of a specialized organization by calling 04 from an unscrupulous place;

Take measures to remove people from the ridden medium, preventing the inclusion of the power off, the appearance of open fire and sparks;

Before the arrival of the emergency brigade, arrange the air ventilation.

2.9 For inspecting and repairing gas pipelines and gas equipment to allow employees of a specialized organization to make any service certificates at any time of the day.

2.10 Provide free access of employees of a specialized organization to the place of installation of liquefied gas cylinders on the day of their delivery.

2.11 Economically spending gas, timely pay its cost, as well as the cost of maintenance and repair of gas equipment.

2.12 To inform the specialized organization when leaving the apartment for more than a month.

2.13 Household owners should timely with specialized organizations enter into contracts for maintenance and emergency dispatching gas equipment and chimney checking, ventilation channels. In winter, should: periodically check the heads in order to prevent their frost and blockage.

3. Owners (users) of apartments (households) are prohibited:

3.1. Produce unauthorized gasification of the house (apartments, garden house), permutation, replacement and repair of gas appliances, cylinders and shut-off valves.

3.2. Refirmation of the room where gas appliances are installed, without coordination with the relevant organizations.

3.3. Make changes to the design of gas appliances. Change the device of flue and ventilation systems, sticking the ventilation channels, tinted or stuck "pockets" and hatches intended for cleaning chimneys.

3.4. Disable security and regulation automation, use gas with faulty gas devices, automation, fittings and gas cylinders, especially when the gas leak is detected.

3.5 Use gas in violation of the density of masonry, plaster (cracks) of gasified furnaces and chimneys. Use heating furnaces with wind wardrobes and open cooking hardware. Self-definition to install additional seams in chimneys and on the chimensing pipes from water heaters.

3.6 Use the gas after the expiration of the act on the inspection and cleaning of flue and ventilation channels

3.7 Use gas devices with closed vents (fraumugas), louvre lattices, lattices of ventilation channels, the absence of thrust in chimneys and ventilation canals, gaps under the doors of bathrooms.

3.8 Leave the operating gas devices unattended, except for those designed for continuous operation and having appropriate automation.

3.9 Admission to the use of gas devices of persons who have not passed the instruction on the safe use of gas in everyday life.

3.10 Use gas and gas devices are not intended. Use gas stoves for the heating of premises.

3.11 Use the premises where gas appliances are installed for sleep and rest.

3.12 Use open fire to detect gas leaks (used soap emulsion or special devices).

3.13 Store indoors and basements empty and filled with liquefied gases cylinders. Selflessly without a special briefing to replace empty cylinders on gas filled and connect them.

3.14 to have in a gasified room more than one balloon with a capacity of 50 (55) l or two cylinders of 27 liters (one of them spare).

3.15 Place the cylinders against the furnaces of the furnaces at a distance less than 2 m from them.

3.16 To allow damage to gas equipment and theft of gas.

3.17 Persons who violated "Instructions for the safe use of gas when satisfying communal domestic needs" are responsible in accordance with the legislation of the Russian Federation.

Ticket 13.

  1. Types of instructions on the safe use of gas in everyday life, conducted with subscribers.
  2. The device and the principle of operation of cranes on gas household plates.
  3. Scope of work when traveling underground gas pipelines.
  4. With what gas pressure is allowed gas cutting and welding on existing external gas pipelines?

Instructing on the safe use of gas in everyday life

5.1. In order to ensure safe use of gas in everyday life, the Gas distribution organization is carried out primary and repeated instructors of gas consumers.

5.2. Specialists of housing and operational organizations responsible for the safe operation of intramonious gas equipment are instructed in a gas distribution organization or training centers at least once every 12 months.

5.3. Primary instruction on the safe use of gas in everyday life:

- before the primary start of gas (natural or liquefied hydrocarbons, including from individual balloon installations) when entering the completed construction of residential buildings into operation, or gasification of existing residential buildings;

- before the establishment of owners (employers) of premises in the ownership of them (contract of hiring) of premises in residential buildings, residential buildings with active ingenious gas equipment;

- When translating the active gas-grade equipment from one type of gas fuel to another.

5.4. Primary instruction on the safe use of gas in everyday life is carried out in a technical office or a specially equipped placement of a gas distribution organization with the use of technical means, visual benefits (posters, layouts, video films, etc.) and existing gas equipment similar to the gas installed in consumers.

5.5. When translating the active gas-grade equipment from one type of gas fuel to another primary briefing can be carried out in rooms occupied on legal grounds of gas consumers, at the end of work.

5.6. Instructing the owners of individual balloon installations using liquefied hydrocarbon gases can be carried out by organizations implementing liquefied hydrocarbon gases in cylinders.

5.8. Persons who have passed primary instructions are registered in the journal of instructing in the instructor of gas consumers, the maintenance and storage of which carries out the gas distribution organization with which the Treaty on the maintenance of intrama gas equipment and emergency dispatching.

5.9. Persons who have passed primary briefings are issued relevant evidence (certificates) and printed instructions for the safe use of gas in everyday life (memo).

5.10. The person who has passed the instruction on the safe use of gas during the operation of individual balloon installations using liquefied hydrocarbon gases is made to write, resolving self-installing and replacing the cylinder.

5.11. Repeated instructions for gas consumers on the safe use of gas in everyday life are carried out by specialists of the gas distribution organization at the end of the maintenance of the maintenance of intrama gas equipment. Instructing can be carried out in the premises held on the legal grounds of gas consumers at the end of work.

5.12. Primary and repeated instructions on the safe use of gas in everyday life, owners (employers) of residential premises or persons, constantly living with them. Gas consumer users are trained in the rules of safe use of Gas in the life of the person who has passed instructing.

Topic Title The content of the instruction Duration, min.
1 2 3
Gas properties Brief information about the chemical composition and odorization of gases. Limits of natural gas explosion, Sug. Physiological impact of gas per person. 5
Gas burning Gas pressure in gas pipelines in a century. Full and incomplete combustion of gas. Flame resistance. Effective and economical use of gas. 5
Gas supply. Gas consumption accounting Gas supply conditions. Gas consumption accounting. Payment for gas supply services, maintenance intern. 5
Instructions for safe use of household gas-grade equipment Device and main technical characteristics of household gas - spreading equipment. Instructions for the use of household gas-grade equipment and care. Organization of maintenance in the LDU. Contents in a good technical condition of the WDGO, the system control systems of the premises. Possible malfunctions and violation of the operating mode of the household gas-wide equipment and how to eliminate them. Possible accidents in violation of the instructions of safe use of gas in everyday life and their consequences. 30
Gas pipelines and fittings General information about the device and design of gas pipelines and reinforcement in the LDW. Methods of attachment and fastening of gas pipelines in a century. The rules of operation of the disconnecting devices on gas pipelines in the LDW. Types of malfunctions and places of possible gas leaks on gas pipelines and fittings in a century, causes of their occurrence, ways to detect. 10
Smoke and ventilation channels Attaching household gas-grade equipment to smoke channels. Device and operation of flue and ventilation channels. Checking the thrust in the flue and ventilation channels, the reasons for its disorders and methods of recovery. The consequences of the work of household gas-wide equipment in violation of thrust in the flue and ventilation channels. Ventilation of the premises in which household gas wicked equipment is installed. Organization of work on maintenance and repair of flue and ventilation channels, content in good condition. 10
Reservoir, Group and Individual Balloon Settings Sug General information about the device, design, basic technical specifications and principles of the operation of reservoir, group and individual balloon installations of the SUG. Possible malfunctions arising from the operation of reservoir, group and individual balloon installations of the SUG. 10
The procedure for replacing the cylinders of Sug Procedure for the replacement of Sug cylinders when connecting group and individual balloon installations 10
Emergency Elimination Measures The actions of the consumers of gas when faults are found in the exhibition of gas in the room, the triggering of systems for controlling the size of the premises, violation of thrust in the flue and ventilation channels. 5
First assistance to victims as a result of avoiding at objects Procedure for first aid for burns, poisoning, suffocation, etc. Sequence of assistance. 10

Cranes

Definitions

3.1 control faucet:The device by which manual gas flow control is carried out in the range specified by the manufacturer.

3.2 flow configuration device:A device that allows manually to pre-adjust the gas consumption through a valve to a given value using calibrated nozzles or an adjusting screw.

3.3 shut-off element:Detail of the crane that opens or closes the gas flow.

3.4 outdoor tightness:The indicator of the presence (absence) leakage. The tightness of the gas tract in relation to the surrounding atmosphere.

3.5 internal tightness:The tightness of the locking element (in the "closed" position), which closes the gas-conducting volume relative to another volume or outlet of the crane.

3.6 gas pressure:Excessive pressure of moving gas relative to atmospheric pressure.

3.6.1 inlet pressure:Gas pressure at the entrance to the crane.

3.6.2 release pressure:Gas pressure at the exit of the crane.

3.6.3 operating pressure:The largest pressure at the input specified by the manufacturer at which the crane is allowed.

3.6.4 pressure drop:The difference between the input and outlet pressures, which depends on the gas flow rate in the "fully open" position.

3.6.5 test pressure:Pressure that must be filed during testing.

3.7 gas consumption:The volume of gas flowing through the crane per unit of time.

3.7.1 nominal flow:Gas consumption specified by the manufacturer provided to standard conditions.

3.7.2 consumption in the "Small Flame" position:The minimum gas consumption specified by the manufacturer, given to the standard conditions.

3.8.1 maximum ambient temperature:The greatest ambient temperature indicated by the manufacturer at which the crane is possible.

3.8.2 minimum ambient temperature:The minimum ambient temperature indicated by the manufacturer at which the crane is possible.

3.9 standard conditions:The ambient temperature is 15 ° C, the atmospheric pressure is 101.3 kPa.

3.10 working cycle:Performing a set of actions to translate crane from closed to the open position and back.

3.11 sealing liner:The shortest distance between gas-conducting parts and atmosphere, measured along the length of the seal surface.

Classification

- by classes - Depending on the number of working cycles during the service life:

A - 5000 cycles (for example, for heating machines and boilers),

In - 10,000 cycles (for example, for air heaters),

C - 40,000 cycles (for example, for gas stoves);

- in groups - Depending on the stresses of tensions in bending and cutting, which they must withstand:

a group of 1 - cranes intended for use in gas devices without affecting them with bending arising during installation of pipelines, due to a number of rigid supports or attachments;

group 2 - cranes designed to install outside or inside the machine without additional fastening or support.

The crane that meets the requirements for group 2 also meets the requirements for group 1.


Similar information.


Instructions for use of gas in everyday life
Citizens who use gas in everyday life should:

1. Periodically go to the instruction on the safe use of the Contractor, to have instructions for the operation of gas-grade equipment and comply with them.

2. Monitor the normal operation of gas-grade equipment, chimneys and ventilation, check the craving to inclusion and during the operation of gas-grade equipment with a discharge of gas combustion products into the chimney.

3. At the end of the use of the gas, close the cranes on gas-grade equipment and in front of it, and when placing a balloon installation (when used as a fuel SUG) indoors, additionally close the valves from balloon installations.

4. If the gas-grade equipment malfunction is caused by the representative of the Contractor.

5. In case of a sudden cessation of gas supply to immediately close the taps of the gas-propelled equipment burners to inform the emergency service "Artist by calling 04, 112" 04 "(on mobile) or 4-26-01.

6. When the smell of gas appears in indoors, immediately stop using gas-wide equipment, block the taps to the equipment and on gas-grade equipment, open the windows or the window to carry out the room. Call the Contractor's emergency-dispatch service by calling 04, 112 "04" (on mobile) or 4-26-01 (outside the ridicated room). Do not light fire, do not smoke, do not include and not turn off the electric light and electrical appliances, do not use the electric lion.

7. Before entering the basements and cellars, before turning on light or ignition fire, make sure there is no smell of gas.

8. When the smell is found in the basement, the entrance, in the courtyard, in the street is necessary:

Notify those surrounding about precautions,

Report 0404, 112 "04" (mobile) or 4-26-01 (from not a ridden place) in the emergency dispatch service of the artist

Take measures to remove people from the ridden environment, preventing the inclusion and off of the electrical displacement, the appearance of open fire or spark;

Before the arrival of the emergency brigade, arrange the air ventilation.

9. Ensure free access of representatives of the Contractor to the place of installation of cylinders with liquefied gas on the day of their delivery.

10 . To inform the artist when leaving the apartment for a period of more than one month.

11. Connecting contracts to check the chimneys and ventilation channels.

Citizens are prohibited:

1. To produce unauthorized gasification of individual households, reinstalling, replacing and repairing gas-wide equipment, cylinders and shock fittings.

2. To redecessing the premises where gas-wide equipment is installed, change the area of \u200b\u200bheated premises, without coordination with the relevant organizations, including with the Contractor.

3. Make changes to the design of gas appliances. Change the device of flue and ventilation systems, sticking the ventilation channels, tinted or stuck "pockets" in hatches intended for cleaning chimneys.

4. Disable security and regulation automation. Use gas with faulty gas-grade equipment, automation, reinforcement and gas cylinders, especially when leakage of gas.

5. Use gas-wide equipment with closed windows (fraumugas), louvre lattices, ventilation channels, lack of traction in chimneys I am ventilation channels, cream under the doors of bathrooms.

6. Leave working gas-wide equipment unattended (except equipment designed for continuous operation and has the appropriate automation for this).

7. To allow for the use of gas-pleasing equipment of preschool children, persons who do not control their actions and not knowing the rules for using this equipment.

8. Use gas and gas wicked equipment is not intended. Use gas stoves for the heating of premises.

9. Use the premises where gas - spreading equipment is installed, for sleep and rest.

10. Apply an open fire to detect gas leaks (soap emulsion and special devices are used for this purpose).

11. Store indoors and basements empty and filled with liquefied gas cylinders.

12. Self remove the replacement of empty cylinders to the filled and connect them.

13. Have in a gasified room more than one balloon with a capacity of more than 50 (55) l. or two cylinders with a capacity of more than 27 liters. Each (one of them is spare).

14. Place the cylinders against the furnaces of the furnaces at a distance of less than 2 meters.

15. To allow damage to gas-grade equipment and theft of gas.

* The Customer and Persons Entering Gas are responsible for the safe operation of gas-wide equipment, for non-fulfillment of the requirements of this Instruction.

In accordance with paragraph 2 of the Decisions of the Government of the Russian Federation of September 9, 2017 N 1091 "On Amendments to Some Acts of the Government of the Russian Federation on Security Provision In the Using and Content of Outdoor and Intra-Quarter Gas Equipment" (Meeting of the Legislation of the Russian Federation, 2017, N 38, Art. 5628), I order:

1. To approve the instructions for the safe use of gas when satisfying communal domestic needs in accordance with the annex to this order.

2. Control over the execution of this order to entrust to the Deputy Minister of Construction and Housing and Communal Services of the Russian Federation A.V. Chibis.

Minister MA Men

Registration No. 50945

application

Approved
order of the Ministry
construction and housing
municipal economy
Russian Federation
dated December 5, 2017 N 1614 / PR

Instructions for safe use of gas when satisfying utility needs

I. General provisions

1.1. Instructions for safe use of gas in the satisfaction of public utilities (hereinafter referred to as the instruction) was developed in accordance with the Decree of the Government of the Russian Federation of May 14, 2013 N 410 "On measures to ensure safety when using and maintaining intra-domestic gas equipment" (Meeting Legislation of the Russian Federation, 2013, N 21, Art. 2648; 2014, N 18, Art. 2187; 2015, N 37, Art. 5153; 2017, N 38, Art. 5628, N 42, Art. 6160).

1.2. The persons responsible for the safe use and content of the intrama gas equipment (hereinafter - the VDGO) and intra-quarter gas equipment (hereinafter - Vggo) are:

with respect to the LDGO in an apartment building - persons carrying out management of apartment buildings that provide services and (or) performing work on the maintenance and repair of common property in apartment buildings (including managing organizations, homeowners, housing cooperatives or other specialized consumer cooperatives) , while directly managed by an apartment house owners of premises in an apartment building - the owners of such premises or one of the owners of premises in such a house or another person who has authority certified by attorney issued by the owners of the premises in an apartment building;

in relation to the union of households - owners (users) of households;

with regard to VGOs - owners (users) of premises located in an apartment building in which such equipment is placed.

II. Instructing on the safe use of gas when satisfying utility domestic needs

2.1. In order to ensure the safe use of gas in the satisfaction of public utilities, the specialized organization with which the maintenance and repair agreement has been concluded and (or) of VKGO, conducts primary and repeated (regular) instruction on the safe use of gas when satisfying communal needs ( Further, respectively, the primary instruction, repeated (next) instruction):

with respect to a centrally apartment building - persons engaged in household houses providing services and (or) performing work on the maintenance and repair of common property in apartment buildings (including managers, partnerships of housing owners, housing cooperatives or other specialized consumer cooperatives) or their representatives, and if directly managed by an apartment building owners of premises in an apartment building - owners of such premises or one of the owners of premises in such a house or other person who has authority certified by attorney issued by the owners of the premises in an apartment building;

in relation to the lion in the household - owners (users) of households or their representatives;

regarding VKGO - owners (users) of premises located in an apartment building in which such equipment is placed or their representatives.

2.2. The primary briefing should be carried out after concluding with a specialized organization of the Treaty on the maintenance and repair of the LDA and (or) of VKGO. The fee for carrying out the primary briefing is not charged.

2.3. The primary briefing should be carried out by a specialized organization before performing work on the primary start-up of gas (including a cylinder with liquefied hydrocarbon gas (hereinafter - the SUG balloon) in a century and (or) of VKGO, as well as in the following cases:

before the establishment of owners (users) in the ownership of them (other legitimate basis), gasified residential premises, except for those in these persons of the document confirming the passage of the primary instruction;

when translating the active household gas-propelled equipment from one type of gas-like fuel to another;

when changing the type (species) of the domestic gas - spreading equipment used;

when translating the current household equipment for the purposes of digestive preparation, heating and (or) hot water supply from solid fuel (coal, firewood, peat) on gaseous.

2.4. The primary briefing should be carried out at the location of the LDGO and / or (or) employee of a specialized organization, relevant to the requirements established by the Rub's Rules in terms of safety when using and maintaining intracerer and intra-quarter gas equipment in the provision of a communal gas supply service approved by the Government Decree of the Russian Federation from May 14, 2013 N 410 (meeting of the legislation of the Russian Federation, 2013, N 21, Art. 2648; 2014, N 18, Art. 2187; 2015, N 37, Art. 5153; 2017, No. 38, Art. 5628; n 42, Art. 6160) (hereinafter referred to as the rules for the use of gas), with the use of technical means and the active household gas-grade equipment, including household gas-grade equipment with an organized tension of combustion products in the smoke channel.

2.6. Primary briefing should include the following information:

the limits of flammability and explosions of hydrocarbon gases (methane, propane, butane), physiological effect on the human hydrocarbon gases, as well as carbon dioxide and carbon monoxide;

composition and properties of gas combustion products, providing air inflows for full combustion of gas, efficient and cost-effective use of gas;

the order of attachment of household gas-grade equipment to smoke channels; device and operation of flue and ventilation channels; Checking the thrust in the flue and ventilation channels, the causes of its violation; the consequences of the work of household gas-grade equipment in violation of thrust in the flue and ventilation channels; Ventilation of the premises in which household gas-priming equipment is installed, the organization of work on verifying the state, cleaning and repairing flue and ventilation channels, content in proper condition;

procedure in the absence (violation) of thrust in the flue and ventilation channels; consequences of using the valve (chiebers) on the flue channels;

main technical specifications, principles of operation, general information about the device, design, appointment and composition of the LDGO and VGGO; Methods of accession and fastening of the LDGO and VGGO, safety rules when using and maintaining a LDGO and VGGO, Types of faults in the LDA and VGGO, the location of possible gas leaks, the causes of their occurrence, methods of detection;

device, design, main technical characteristics, placement and principles of operation of reservoir, group and individual balloon installations with liquefied hydrocarbon gas (hereinafter - Bulone installations SUG); Possible malfunctions arising from the use of reservoir, group and individual balloon installations of the SUG, the consequences of their overflow and heating of the Sug Ballon; Rules for the storage and procedure for the replacement of balloon installations of the SUG;

actions when the faults are detected in the LDGU and VGG, the detection of leakage (smell) of the gas in the room, the triggering of the alarms or systems for controlling the size of the premises;

rules for the first aid for burns, frostbite (for balloon installations of SUG), poisoning, suffocation, electric shocks.

2.7. Persons who have passed primary briefings are registered in the primary instructional instruction journal on the safe use of gas in the satisfaction of communal domestic needs, the maintenance and storage of which is carried out by a specialized organization.

2.8. The person who has passed the primary briefing is issued a copy of the instructions, as well as a document confirming the passage of the primary briefing.

2.9. Repeated (regularly) briefing of the persons specified in paragraph 2.1 of the instructions should be carried out by a specialized organization with the next maintenance of the LDGO and (or) of VKGO. The fee for holding a repeated (next) briefing is not charged.

2.10. The owner (user) of household or dwelling in an apartment building or his representative, which has passed the primary or repeated (regular) instruction, must acquaint the requirements of the instructions of all persons permanently residing with him in the residential premises.

III. Rules of safe use of gas by persons carrying out enterprise apartment buildings providing services and (or) work on the maintenance and repair of common property in apartment buildings

3.1. Persons engaged in managing apartment buildings and (or) performing work on the maintenance and repair of common property in apartment buildings, it is necessary:

3.1.1. If the gas leakage is detected and the (or) triggering of the alarms or system of gas zagaznosts, perform the actions listed in Chapter V instructions.

3.1.2. Assign a person responsible for the safe use and content of the FDGU, which must undergo primary briefing with the use of technical means and the active household gas-grade equipment, including household gas-wide equipment with an organized branch of combustion products in the smoke channel.

3.1.3. Provide proper content of flue and ventilation channels, including independently (if there is a license issued in the manner prescribed by the Regulations on the licensing of installation, maintenance and repair activities of buildings and structures, approved by Decree of the Government of the Russian Federation of December 30, 2011 G. N 1225 (Meeting of the legislation of the Russian Federation, 2012, N 2, Art. 298; 2015, N 19, Art. 2820; 2017, N 42, Art. 6160) (hereinafter referred to), or under a contract with an organization having A license, timely and efficiently carry out the state and functioning of the flue and ventilation channels, the presence of traction, as well as, if necessary, cleaning and (or) repair of flue and ventilation channels (including channels of channels).

3.1.4. Prior to the start of the work on checking the condition, cleaning and repairing flue and ventilation channels, notify the owner (user) of the room in an apartment building about the need to disable household gas-grade equipment for the period of these works.

3.1.5. In the heating period, ensure the prevention of frost and blockage of the headings of the flue and ventilation channels.

3.1.6. In the event of an improper state of smoke and (or) ventilation channels of an apartment building, immediately notify the owners (users) of premises in an apartment building about the inadmissibility of the use of household gas-grade equipment.

3.1.7. To ensure proper operation of the LDU.

3.1.8. Immediately inform the emergency-dispatch service of a gas distribution organization about the detection of the following violations:

the presence of gas leakage and (or) triggering of the alarms or systems for controlling the size of the premises;

the deviation of the gas pressure from the values \u200b\u200bstipulated by the rules for the provision of utilities to the owners and users of premises in apartment buildings and residential buildings, approved by Decree of the Government of the Russian Federation of May 6, 2011 N 354 (Meeting of the Legislation of the Russian Federation, 2011, N 22, Article 3168 ; 2012, N 23, Art. 3008; N 36, Art. 4908; 2013, N 16, Art. 1972; N 21, Art. 2648; N 31, Art. 4216; N 39, Art. 4979; 2014, n 8, Art. 811; N 9, Art. 919; N 14, Art. 1627; N 40, N 5428; N 47, Art. 6550; N 52, Art. 7773; 2015, N 9, Art. 1316; n 37, Art. 5153; 2016, N 1, Art. 244; N 27, Art. 4501; 2017, N 2, Art. 338; N 11, Art. 1557; N 27, Art. 4052; N 38, Art. 5628; Official Internet portal of legal information www.pravo.gov.ru, April 3, 2018, N 0001201804030028) (hereinafter - rules for the provision of utilities);

unauthorized overlap of shut-off reinforcement (cranes) installed on gas pipelines included in the FDGO;

accident or other emergency that has arisen when using gas.

3.1.9. Ensure the availability of project, operational and other technical documentation, including confirming the proper technical condition of the intensity, flue and ventilation channels, as well as submit copies of the specified documents at the request of a specialized organization authorized by the executive authorities of the constituent entities of the Russian Federation, carrying out the regional state housing supervision ( Further, the state housing supervision) and authorized bodies of local governments, carrying out municipal housing control (hereinafter referred to as the bodies of municipal housing control).

3.1.10. To ensure the safety of the Treaty on maintenance and repair in a century and (or) of VKGO, the Treaty on the Technical Diagnosing Treaty of the LDGU and (or) of the VKGO (if available), as well as the acts of acceptance of the work performed (services rendered), notifications (notifications) of a specialized organization, Supplier of gas, prescriptions of the state housing supervisory authorities and bodies of municipal housing control.

3.1.11. Provide timely maintenance, repair, technical diagnostics and replacement of the LDGU and (or) VKGO.

3.1.12. Not later than 10 working days before the planned break of the filing and (or) reduction in the working pressure of cold water to inform the owners (users) of premises in an apartment building, in which heat generators are placed on the timing of such a break.

3.1.14. No less often, 1 time in 10 working days, check the basements of basements, cellars, subliments and technical floors with fixing the results of control in the journal of inspections indicating the dates of conducting inspections, the persons they have been conducted, the premises in which inspections were conducted, the results of the inspections.

3.1.15. Before entering the basements, cellar, the underground and technical floors before turning on the electrical displacement or ignition of the fire to make sure that there are no gas supply of the specified premises.

3.1.16. Initially take action on the execution of notifications (notices) of a specialized organization, as well as the prescriptions of the state housing supervisory authorities and bodies of municipal housing control.

3.1.17. At any time of the day, ensure unobstructed access to the premises in which the LDGO is placed, as well as to assist in ensuring access to the Employees of the Emergency Management Service of the gas distribution organization, as well as other emergency services in order to prevent, locate and eliminate accidents related to the use of and the content of the LDA and (or) VKGO.

3.1.18. Provide air flow into the room in an apartment building, in which gas-grade equipment is installed in the extent. At the same time, at the bottom of the door or wall, which goes into the adjacent room, it is necessary to provide a lattice or gap between the door and floor, as well as special supply devices in the outer walls or windows of the specified room.

3.1.19. Based on the Treaty on Maintenance and Repair of the LDA and / OR) of the VKGO and the Treaty on the Technical Diagnosing Treaty of the LDA and / or (or), to provide representatives of the specialized organization to access to the LDA, as well as to promote them access to VKGO in order to:

conducting preventive and unscheduled works aimed at the safe use of the inventory and (or) VKGO;

suspension, resumption of gas supply in cases stipulated by gas use rules, rules for the provision of utilities, gas supply rules to ensure the public utilities of citizens approved by the Decree of the Government of the Russian Federation of July 21, 2008 N 549 (Meeting of the Legislation of the Russian Federation, 2008, N 30, Art. 3635; 2011, N 22, Art. 3168; 2013, N 21, Art. 2648; 2014, N 8, Art. 811; 2014, N 18, Art. 2187; 2017, N 38, Art. 5628) (hereinafter referred to as Gas Supply Rules).

IV. Rules for safe use of gas by owners (users) of households in relation to the lifting and premises in apartment buildings in relation to VG

4. Owners (users) of households and premises in apartment buildings need:

4.1. Know and follow the instructions.

4.2. If the gas leakage is detected and the (or) triggering of the alarms or system of gas zagaznosts, perform the actions listed in Chapter V instructions.

4.3. Monitor the state of flue and ventilation channels, contain chimney cleaning pockets, check the presence of thrust to inclusion and during the operation of household gas-wide equipment.

4.4. Ensure the extraction of the valve (chiiter) when it is presented from the design of the heating household furnace with an installed gas-melting device and sealing from the outer side of the wall of the smoke channel of the resulting hole (gaps).

4.5. There is a preliminary ventilation of the combustion chamber in front of the burner of the household gas-grade equipment (furnace furnace furnaces) for 3-5 minutes.

4.6. After the end of the use of the gas, closes the cranes on the household gas-wide equipment, and when placing a cylinder SUG inside the household or premises in an apartment building - to additionally close the valve of the cylinder.

4.7. Immediately report to the emergency dispatch service of a gas distribution organization about the discovery of the following facts:

the presence of gas leakage and (or) response of the alarms or systems for controlling the size of the premises;

lack or impairment of thrust in flue and ventilation channels;

deviation of the gas pressure from the values \u200b\u200bprovided for by the rules for the provision of utilities;

suspension of gas supply without prior notice from a specialized organization or gas supplier;

unauthorized overlap of shut-off valves (cranes) located on gas pipelines that are part of the FDGO;

damage to the LDGO and (or) VKGO;

accident or other emergency emerging when using gas;

leaky through the lifting and (or) of the leakage currents, closure on the body of household gas-grade equipment and equalized currents.

4.8. Before entering the basements and cellar to the inclusion of the electrical displacement or ignition of the fire, make sure that there is no reason for the placement.

4.9. Provide during the deadlines established by federal laws, other regulatory legal acts of the Russian Federation, storage:

notifications (notices) of a specialized organization, gas supplier, prescriptions of the state housing supervisory authorities and bodies of municipal housing control;

technical documentation on the ESTN and (or) of VKGO, copies of which should be submitted in a timely manner at the request of a specialized organization, state housing supervisory authorities and bodies of municipal housing control;

treaty on maintenance and repair in a century and (or) VKGO, a contract for the technical diagnostics of the FNGO and (or) of the VKGO (if any), as well as acts of acceptance of the work performed (services rendered).

4.10. Provide timely maintenance, repair, technical diagnostics and replacement of the LDGU and (or) VKGO.

4.11. Timely take measures to fulfill the notifications (notices) of a specialized organization, as well as the prescriptions of the state housing supervision bodies and bodies of municipal housing controls in terms of compliance with the obligatory requirements for the availability of a contract for the maintenance and repair of the FNIG and (or) of the VKGO with a specialized organization, relevant requirements, Installed rules for using gas.

4.12. At any time of the day, ensuring unobstructed access to the premises in which the inventory and (or) of VKGO, employees of the emergency dispatch service of the gas distribution organization, as well as other emergency operational services in order to prevent, locate and eliminate accidents related to the use and content of the LDGO and (or) VKGO.

4.13. In the event of the upcoming absence of persons more than 24 hours in a room in an apartment building, close the shut-off valves (cranes), located on branches (omens) to household gas-grade equipment, except for the heating household gas-wide equipment, designed for continuous operation and equipped with appropriate automatic security.

4.14. To close the shut-off valves (cranes) located on branches (omens) to heating household gas-grade equipment, including designed for continuous operation and equipped with appropriate security automatic security, in the event of the coming absence of persons more than 48 hours in a room in an apartment building.

4.15. Provide the access of representatives of a specialized organization, a gas supplier to a century and (or) VKGO in order to:

carrying out maintenance, repair, installation, replacement, technical diagnostics of the inventory and (or) VKGO;

suspension of gas supply in cases stipulated by gas use rules, rules for the provision of utilities, gas supply rules.

4.16. Monitor the serviceability of household gas-wide equipment.

4.17. To ensure the proper technical condition of the LDGO and (or) of VKGO, gas metering devices and the safety of the seals installed on them.

4.20. Install (place) Furniture and other flammable items and materials at a safe distance from domestic gas-grade equipment in accordance with the requirements of fire safety standards.

4.21. Provide an air flow into the room in which the gas-grade equipment is installed, which is part of the inventory and / or (or) VK. At the same time, at the bottom of the door or wall, which goes into the adjacent room, it is necessary to provide a lattice or gap between the door and floor, as well as special supply devices in the outer walls or windows of the specified room.

V. Actions when a gas leakage is detected

5.1. When indoors (home ownership, apartment, stairwell, basement, cellar and other), gas leaks and (or) triggery of the alarms or systems for controlling the size of the premises are necessary to take the following measures:

immediately stop using household gas-wide equipment;

overlap the shut-off valves (cranes) on the household gas-grade equipment and on a branch (vacation) to it;

when placing a cylinder SUG inside home ownership or premises in an apartment building - additionally close the valve of the Sug Ballon valve;

immediately ensure the influx of air into the premises in which the gas leak is detected;

in order to prevent the appearance of the spark, do not include and do not turn off the electrical devices and equipment, including electric lighting, electrical connections, radio electronic communications (mobile phone and other);

do not light fire, do not smoke;

take measures to remove people from the ridden environment;

recoverate (subject to availability) about the precautionary measures of people in adjacent rooms in an apartment building, including in premises related to the common property of the owners of premises in an apartment building (in the entrance, corridor, stairwell and other);

leave the room in which the gas leak was detected, and go to a safe place, from where to report on the presence of gas leakage by phone in the emergency-dispatch service of the gas distribution organization (when calling from a mobile phone to dial 112, when calling from a stationary phone to type 04), as well as If necessary, other emergency operational services.

Vi. Rules for the treatment of the LDA and VKGO persons carrying out the management of apartment buildings providing services and (or) performing work on the maintenance and repair of common property in apartment buildings, owners (users) of households and premises in apartment buildings

6. Persons engaged in the management of apartment buildings providing services and (or) performing work on the maintenance and repair of common property in apartment buildings, owners (users) of households and premises in apartment buildings should not:

6.1. To perform actions on the installation of gas pipelines of gas consumption networks and their technological connection to the gas distribution network or other gas source, as well as on the connection of household gas-grade equipment to a gas pipeline or a reservoir, group or individual balloon installation of a South without compliance with the requirements provided by the legislation of the Russian Federation (unauthorized gasification);

6.2. To carry out a violation of the legislation of the Russian Federation, the reorganization of the inventory and (or) of VKGO, flue and ventilation channels.

6.3. Close (tinning, sticking) holes of flue and ventilation channels, hatches of chimney cleaning pockets.

6.4. To carry out unauthorized reorganization and (or) redevelopment of the premises in which the intensifier and (or) of VKGO, without coordination with the local government body in the manner prescribed by the housing legislation of the Russian Federation.

6.5. Alone without the involvement of a specialized organization, check the operation of the alarms or system control systems for the size of the premises.

6.6. Install the valve (Sewber) on the smoke channel, chimney, chimney.

6.7. Use, install a gas-melting device in heating household ovens when placed in rooms of apartment buildings.

6.8. Use, install household gas-wide equipment, the capacity of which exceeds the values \u200b\u200ballowed by the regulatory legal acts of the Russian Federation, technical documents and project documentation.

6.9. Disrupt the preservation of seals installed on gas metering devices.

6.10. Unimpressive connecting in a century and (or) of VKGO, including domestic gas-wide equipment after it is turned off by a specialized organization or gas distribution organization, including those who are part of its emergency dispatch service, as well as other emergency operational services.

6.11. Connect chims from domestic gas-grade equipment to ventilation channels.

6.12. Make changes to the design of flue and ventilation channels, the holes of which are indoors with installed household gas-wide equipment.

6.13. Disconnect the security automation of household gas-wide equipment.

6.14. To use inventory and / or (or) in the designs of which connect to the electrical network or the presence of galvanic elements (batteries), without compliance with the requirements of manufacturers.

6.15. Leave unattended household gas-wide equipment, except for equipment designed for continuous operation and equipped with appropriate security automation, during the period of time specified in paragraphs 4.13 and 4.14 instructions.

6.16. To allow for the use of domestic gas-pleasing equipment for children of preschool age, persons who do not control their actions, persons with disabilities that do not allow to safely use household gas-wide equipment, as well as persons who have not been instructed on the safe use of gas when satisfying utility needs.

6.17. Leave in the open position of the cranes on the domestic gas-wide equipment without ensuring the ignition of the gas-air mixture on gas-melting devices for more than 5 seconds.

6.18. Use open fire, turn on or off electrical appliances and equipment, including electric lighting, electric connections, radio electronic communications (mobile phone and other) in cases:

fulfillment of maintenance and repair work and (or) VKGO;

gas leak detection;

the triggering of the alarms or systems for controlling the size of the premises.

6.19. Limit representatives of a specialized organization, gas supplier access to a century and (or) in foreign objects (including furniture) for work, providing appropriate use and maintenance of the LDGO and (or) VKGO.

6.20. To use a century and (or) VKGO is not intended, including:

to give the room with household gas-grade equipment intended for cooking;

tie to gas pipelines that are part of the FDI and (or) VKGO, foreign items (ropes, cables and other);

use gas pipelines as supports or earthing;

dry clothes and other items above the household gas-wide equipment or near it;

expand and (or) engagement with static or dynamic loads.

heating coal, coke or other types of solid fuel heating household furnaces designed to work on gaseous fuel.

6.21. Use for sleep and leisure the premises in which household gas wicked equipment is installed.

6.22. Twisting, transmit, climb, stretch or clamp gas hoses connecting household gas-wide equipment with a gas pipeline.

6.23. Check the operation of ventilation channels, tightness of the connections in a century and (or) VKGO using sources of open flame, including matches, lighters, candles and other.

6.24. Allow damage and damage to the LDA and (or) VKGO, theft of gas.

6.25. Selflessly without the passage of a special briefing or without submitting an appropriate application to a specialized organization to replace the empty cylinders of the SUG, as well as connect the cylinders of the SUG to domestic gas-grade equipment.

6.26. Store Sug Cylinders in residential buildings, rooms in apartment buildings, as well as on evacuation paths, stairwells, basement floors, in basement and attic rooms, on balconies and balconies.

6.27. Place inside houses, premises in apartment buildings Cylinders SUG for domestic gas-wide equipment, with the exception of 1 cylinder connected to the household gas stove of factory manufacture, the volume allowed by the Firewar Regulations in the Russian Federation, approved by the Decree of the Government of the Russian Federation of April 25, 2012 N 390 (Meeting of the legislation of the Russian Federation, 2012, N 19, Art. 2415; 2014, N 9, Art. 906; N 26, Art. 3577; 2015, N 11, Art. 1607; N 46, Art. 6397; 2016 , N 15, Art. 2105; N 35, Art. 5327; N 40, Art. 5733; 2017, N 13, Art. 1941; N 41, Art. 5954; N 48, Art. 7219; 2018, N 3, Art. 553).

6.28. Subject to the cylinder SUG solar and other thermal exposure.

6.29. Install (place) Furniture and other flammable items and materials without compliance with the requirements for distances from domestic gas-wide equipment established by the legislation of the Russian Federation in the field of fire safety.

6.30. Place the Sug Cylinder at a distance less than 0.5 m from the household gas plate (with the exception of built-in cylinders), 1 m to heating devices, 2 m to the burners of heating household furnaces, less than 1 m from the electric meter, switches and other electrical devices and equipment.

6.31. Allow the contact of electrical wires with Sug cylinders.

6.32. Place a balloon installation of Emergency exits, from the main facades of buildings.

6.33. Turn over, placed with a deviation from the vertical or in an unstable position of the Sug cylinder connected to the household gas-grade equipment.

6.34. Use inventory and (or) in the following cases:

6.34.1. Lack of maintenance and repair agreement in a century and (or) VKGO concluded with a specialized organization.

6.34.2. Lack of thrust in chimneys and ventilation channels.

6.34.3. The absence of air inflows in the amount required for the full combustion of gas, including for the following reasons:

the absence or foundation in the closed position of the adjustable window sash, fraumuga, vectors, a special supply device in the outer walls or windows, the closed position of the louvre lattice on the ventilation channel in the room in which household gas wicked equipment is installed;

using indoors in which household gas-priming equipment is installed with a discharge of combustion products into the smoke channel, electrical mechanical motivation devices that are not provided for by project documentation.

6.34.4. The lack of timely verification of the state of the flue and ventilation channels.

6.34.5. Lack of hermetic compound of chimney from domestic gas-wide equipment with a smoke channel.

6.34.6. The presence of impaired integrity and density of brick masonry (the presence of cracks, destruction), the tightness of the flue and ventilation channels.

6.34.7. Availability of valves (chieber) on a flue channel, chimney, chimney.

6.34.8. The presence of safety automation malfunction.

6.34.9. The presence is unreasonable in the process of maintenance of gas leakage.

6.34.10. The presence of a malfunction, uncompleteness or unsuitability for the repair of the LDA and (or) VKGO.

6.34.11. The presence of an unauthorized connection of the LDA and / or (or) ingress to the gas distribution network gas pipeline or other gas source.

6.34.12. The presence of an emergency condition of building structures of a household or an apartment building, in the premises of which installed in a century and (or) VKGO.

6.34.13. The existence of an existed regulatory life or service life established by the manufacturer, in a century and (or) of VKGO (individual equipment included in the FDI and (or) VKGO) in the absence of a positive conclusion according to the results of technical diagnostics of the specified equipment, and in case of extension This period is based on the results of technical diagnostics - the presence of an expired extended life of the specified equipment.

Overview of the document

Approved instructions for the safe use of gas when satisfying communal domestic needs.

Persons responsible for the safe use and maintenance of intramanema gas equipment (VGGO) and intra-ordinary gas equipment (VKGO) are identified.

With respect to the LDGO in an apartment building (MD), these are the management of MD, providing services and (or) performing work on the maintenance and repair of common property, and with the direct managers of MD owners of the premises in it - the owners of such premises or one of the owners or other A person who has authority certified by the attorney issued to him by all or most owners of the premises.

In relation to the lion in household, it is the owners (users) of households.

With regard to VGOs - owners (users) of premises located in an apartment building in which such equipment is placed.

The organization with which an agreement on the maintenance and repair of the LDGO and (or) of the VKGO is carried out for listed persons primary and repeated (next) instructing on the safe use of gas in the satisfaction of utility needs.

Stipulated rules for the safe use of gas; actions when a gas leakage is detected; Actions that should not be committed to responsible persons.